Please enable JavaScript to view this site.

Navigation: Wiring

Wiring ModuleX5

Scroll Prev Top Next More

 

Before proceeding please check which Module-X model is being connected.

This chapter is about Module-X5 [GK_MX5]

 

 

Module-X with pigtail:

 

The Module-X comes with a pigtail existing of:

 

1.I/O cable

Version: v5- AV0017-04 -TRVVSP *7P+F+AL +B OD:8. 7±0.2mm

2.Ethernet cable

Module-X4 with dual pigtail

 

 

 

 

Wiring diagram of the Module-X5 - I/O cable

 

To connect the Paxton Net2 Plus controller, adhere to the following schematic.
Make sure to establish connections to D0, D1, Wiegand GND in and Wiegand +12V in.

 

 

P1

Color

Description


1

orange

RS485- (B)


2

white/red

Wiegand D0


3

black

Relay_B COM


4

white/black

Relay_A NO


5

red

Wiegand D1


6

black/orange

RS485+ (A)


7

brown

GND - NOT USED


8

black/brown

Relay_B NO


9

blue

Relay_A COM


10

black/blue

CTL IN1

>2.2=high

11

green

EXT power in GND


12

black/green

Wiegand / OSDP GND in


13

yellow

EXT power in

24VDC~48VDC

14

black/yellow

Wiegand / OSDP +12V in